Hardware points
As of Mervis IDE 2.3.0.x, for the FreeRTOS platform there is load evaluation as HW points (which is just a measure of processor and memory load, these hardware points have nothing in common with physical data points - inputs and outputs). The HW points add with added channels and devices. After compilation, the HW points utilisation is listed in the Output tab.
Overview of HW points for PLC with FreeRTOS operating system:
PLC | SoftPLC link | IEC 62056-21 | M-Bus | BACnet UDP | BACnet UDP server | Modbus serial | Modbus TCP | Modbus server serial | Modbus server TCP |
mark100 - max. 119 p. | 30 p. (+2 p. per device) | 34 p. | 34 p. | Protocol not supported | Protocol not supported | 29 p. | 29 b. (+2 p. per device) | 27 p. | 29 p. |
mark100v2 - max. 119 p. | 30 p. (+2 p. per device) | 34 p. | 34 p. | Protocol not supported | Protocol not supported | 29 p. | 29 b. (+2 p. per device) | 27 p. | 29 p. |
mark120 - max. 94 p. | 30 (+2 p. per device) | Protocol not supported | Protocol not supported | Protocol not supported | Protocol not supported | Protocol not supported | 30 (+2 p. per device) | Protocol not supported | 30 |
mark125 - max. 443 p. | 30 (+2 p. per device) | 30 | 34 | 24 | 23 | 30 | 30 (+2 p. per device) | 28 | 30 |
mark150 - max. 118 p. | 30 (+2 p. per device) | 34 | 34 | Protocol not supported | Protocol not supported | 30 | 30 (+2 p. per device) | 27 | 29 |
mark150s - max. 119 p. | 30 (+2 p. per device) | 34 | 34 | Protocol not supported | Protocol not supported | Protocol not supported | 27 (+2 p. per device) | Protocol not supported | 29 |
mark150/485 - max. 118 p. | 30 (+2 p. per device) | 34 | 34 | Protocol not supported | Protocol not supported | 30 | 30(+2 p. per device) | 27 | 29 |
mark150/485s - max. 118 p. | 30 (+2 p. per device) | 34 | 34 | Protocol not supported | Protocol not supported | 30 | 30 (+2 p. per device) | 27 | 29 |
IMIO100 - max. 118 p. | 30 (+2 p. per device) | Protocol not supported | Protocol not supported | Protocol not supported | Protocol not supported | Protocol not supported | 30 (+2 p. per device) | Protocol not supported | 30 |
IMIO105 - max. 466 p. | 30 (+2 p. per device) | 30 | 34 | 24 | 23 | 30 | 30 (+2 p. per device) | 28 | 30 |
IMIO110 - max. 443 p. | 30 (+2 p. per device) | 30 | 34 | 24 | 23 | 30 | 30 (+2 p. per device) | 28 | 30 |
ICIO200 - max. 114 p. | 30 (+2 p. per device) | 30 | 34 | 24 | 23 | 30 | 30 (+2 p. per device) | Protocol not supported | 30 |
ICIO205 - max. 466 p. | 30 (+2 p. per device) | 30 | 34 | 24 | 23 | 30 | 30 (+2 p. per device) | 28 | 30 |
If the maximum recommended amount of HW points is exceeded, the warning can be ignored by checking Ignore points in PLC properties, and redeploying the project. However, for correct and safe PLC operation, this is not recommended. The PLC may lack resources for other processes, and e.g. web server response may be worse.