Single alarm memory
Block name
BD49_SINGLEALARMMEMORY
ST call
PROGRAM TEST_BD49 VAR BOOL1, BOOL2, BOOL3:BOOL; FB : LIB.CORE.V1_0.BD49_SINGLEALARMMEMORY; END_VAR FB(IN:=BOOL1, RESET:=BOOL2); BOOL3 := FB.MEMORY; END_PROGRAM
Library
LIB\CORE
Version
V1.0
Description
This block is dedicated to deal with alarm states. The alarm signal is at the IN input. A rising edge on the IN input sets MEMORY to TRUE (alarm memory). The alarm can be reset by a rising edge at the RESET input. If IN=FALSE at the reset time, then MEMORY goes to FALSE. If the alarm is active (IN=TRUE), it can not be reset by the RESETinput, but may be acknowledged by a rising edge brought to the ACK input.
Inputs
| Input | Type | Description | Default value |
| IN | BOOL | Input of the alarm signal | False |
| ACK | BOOL | Acknowledge. If IN=TRUE and rising edge comes to ACK then ACKNOWLEDGED=TRUE (while keeping MEMORY=TRUE) | False |
| RESET | BOOL | Reset of the alarm memory and ACKNOWLEDGED output | False |
Outputs
| Output | Type | Description |
| ACKNOWLEDGED | BOOL | Indication that an alarm has been acked |
| MEMORY | BOOL | Alarm memory |
| ALRSTATUS | INT | Status of the alarm block (bit 8 indicates IN=TRUE, bit 9 indicates ACKNOWLEDGED=TRUE, bit 10 indicates MEMORY=TRUE) |