Switcher Block (v3.0)
Description
- Full function block name: Lib.Mervis.v3_0.SwitcherBlock
- Inherits from: Lib.Mervis.v2_0.BaseAlarmBlock
- Required project references: Lib.Mervis
ST call
PROGRAM PUMP_CONTROL_DEMO VAR Heating_Demand : BOOL; Pressure_Switch : BOOL; Thermal_Fault : BOOL; PumpSwitcher : Lib.Mervis.v3_0.SwitcherBlock; Pump_Relay : BOOL; END_VAR PumpSwitcher( Demand := Heating_Demand, Feedback := BOOL_TO_USINT(Pressure_Switch), Failure := Thermal_Fault, RunDown := T#2m, // 2 minutes overrun to cool down FeedbackTimeout := T#10s // Wait 10s for pressure to build up ); Pump_Relay := PumpSwitcher.Command; END_PROGRAM
Inputs
| Name | Data Type | Allowed Range | Retain | Required | Description |
|---|---|---|---|---|---|
| OperatingMode | OperatingModeType | Yes | No | Desired operating mode. The “Off” mode is dominant and prevents starting by any other function. | |
| Demand | bool | No | Yes | Industry standard for “Requesting” an operational state in automatic mode. Often used in “Call for Heat” scenarios to avoid confusion with economic “Supply/Demand” terms. | |
| Feedback | usint | 0..2 | No | No | Running status feedback. Describes the logic requirement of waiting for confirmation while a Command is active (e.g., a fan dependent on pressure differentiation). You can directly map a boolean feedback using BOOL_TO_USINT. |
| FeedbackManual | bool | No | No | Feedback indicating a manual hardware override (e.g., HOA switch on the cabinet panel). | |
| Failure | bool | No | No | External hardware fault report. Clarifies the source is hardware, not logic. Triggered by external reports like a motor trip, thermal overload, or frequency inverter fault. | |
| EmergencyShutdown | bool | No | No | Emergency stop command. Overrides all modes. | |
| OperatingHoursReset | bool | No | No | Trigger to reset the accumulated operating hours counter. | |
| RunDown | time | No | No | Overrun / post-run time. HVAC standard for heat dissipation cycles to safely dissipate residual heat. The device will continue running for this duration after Demand is removed. If zero, the function is disabled. | |
| FeedbackTimeout | time | No | No | Time allowed for the feedback signal to become active after the Command is issued before an alarm is raised. | |
| KickFunctionInterval | time | No | No | Interval for the periodic maintenance/exercise function. Ensures the system is used regularly to maintain fluid movement and prevent seizing (e.g., run every 7 days). If zero, disabled. | |
| KickFunctionDuration | time | No | No | How long the device should run during the periodic maintenance/exercise kick to maintain fluid movement and prevent seizing. | |
| NotRunAlarmPriority | AlarmPriorityType | No | No | Alarm class for the “Fail to Start” (Not running) alarm. | |
| FailureAlarmPriority | AlarmPriorityType | No | No | Alarm class for the external Failure alarm. | |
| EmergencyAlarmPriority | AlarmPriorityType | No | No | Alarm class for the Emergency Shutdown alarm. | |
| ControlFlags | uint | 0..15 | No | No | Bit array defining extended block behavior (see table below). |
Description of Feedback values
| Value | Meaning |
|---|---|
| 0 | Feedback is inactive (Not running) |
| 1 | Feedback is active (Running) |
| 2 | Feedback is not connected (Default value - ignores feedback logic) |
Description of ControlFlags values
| Bit | Mask | Meaning |
|---|---|---|
| 0 | 1 | If TRUE (1), all alarm evaluations are completely disabled. |
| 1 | 2 | Defines Command output behavior during an alarm in Automatic mode. If TRUE, Command is deactivated on alarm. |
| 2 | 4 | Defines Command output behavior during an alarm in Manual mode. If TRUE, Command is deactivated on alarm. |
| 3 | 8 | Defines the alarm reaction to EmergencyShutdown. If TRUE, an Emergency Shutdown will trigger a Failure alarm. |
| 4..15 | - | Unused |
Outputs
| Name | Data Type | Description | |
|---|---|---|---|
| Command | bool | The operational command output (TRUE = Run, FALSE = Stop). | |
| AlarmsInterface | ptr_to BaseAlarmBlock | Composite interface pointer for unified alarm indication handling. | |
| CompositeState | uint | Bit array describing the complete internal state of the block. | |
| OperatingHours | time | Total accumulated running time of the device. | |
| StartCounter | udint | Total number of times the device has been started. |
Description of CompositeState output values
| Bit | Mask | Meaning |
|---|---|---|
| 0 | 1 | Command is active. |
| 1 | 2 | Feedback is active. (If Feedback = 2, this simply mirrors the Command state). |
| 2 | 4 | Manual Mode is active. |
| 3 | 8 | Manual On is active. |
| 4 | 16 | Demand is active. |
| 5 | 32 | Kick (Periodic exercise) is currently active. |
| 6 | 64 | Run-down (Overrun) is currently active. |
| 7 | 128 | Failure/Fault is present. |
| 8-9 | - | Current OperatingMode representation. |
Detailed Function Description
This block integrates standard, highly-used functionalities required for safely and effectively switching physical devices (such as pumps, fans, or compressors). The core capabilities include:
- Operating Modes: Supports Auto, Manual OFF, and Manual ON logic.
- Feedback Monitoring: Verifies that the physical device has actually started.
- Alarm Management:
- Not Run (Fail to Start): Triggered if the block issues a Command, but the physical Feedback does not become active within the FeedbackTimeout period.
- Failure: Triggered by an external fault signal mapped to the Failure input, or optionally by an EmergencyShutdown.
- Periodic Kick (Exercise Function): Prevents mechanical seizing (e.g., pump rotors during summer) by automatically running the device for a short duration at set intervals.
- Run-Down (Overrun): Keeps the device running for a specified time after the demand has ceased (crucial for dissipating residual heat).
- Emergency Shutdown: Instantly halts the device, overriding all internal logic.
- Maintenance Counters: Tracks total operating hours and start counts.
Execution Logic: A switch command is generated based on the Demand input (in Auto mode) or forced by the Manual ON mode. Once the Command is active, the block monitors the Feedback. If the feedback is not detected within the FeedbackTimeout, a Not Run alarm is generated.
If an external fault occurs (e.g., a frequency inverter fault or thermal overload), the Failure input generates a Failure alarm. Setting the EmergencyShutdown input to TRUE immediately deactivates the Command regardless of the selected operating mode.
In Automatic mode, the device may also start independently of the Demand if the KickFunctionInterval expires. It will run strictly for the KickFunctionDuration.
When the Demand becomes inactive, the run-down timer begins. The Command remains active for the duration specified by RunDown, ensuring safe shutdown procedures (like cooling down a boiler loop) are completed before the relay is finally deactivated.
Application Example from a Real Project
This block is highly recommended for controlling physical outputs like circulation pumps or exhaust fans.
Scenario: Heating Circulation Pump In a standard commercial boiler room, a circulation pump must run whenever the heating controller requests heat (Demand). However, abruptly stopping the pump when the burner turns off can cause water to boil in the heat exchanger due to residual heat.
- By configuring the RunDown property to `T#2m`, the pump will continue circulating water for 2 minutes after the demand stops.
- During the summer, the pump is turned off for months. To prevent the impeller from seizing due to rust or sediment, the KickFunctionInterval is set to `T#7d` (7 days) and the KickFunctionDuration to `T#30s`.
- A differential pressure switch is wired to the Feedback pin. If the PLC turns the pump on but detects no water pressure within 10 seconds (FeedbackTimeout), it triggers an alarm to alert the facility manager of a broken belt or seized motor.