Alarm Trigger for Boolean Variables (8 Inputs)
Full Name
Lib.Mervis.v1_0.bool8_to_alrtrig
Required Project References
- Lib.Mervis
Description
Auxiliary block used for generating alarms for up to eight boolean variables.
Usage in ST
program test
var
inp: lib.mervis.v1_0.bool8_to_alrtrig;
end_var
inp();
end_program
Inputs
| Inputs | Name | Data Type | Retain | Required Connection | Meaning |
| Input1 Input2 Input3 Input4 Input5 Input6 Input7 Input8 | bool | No | Yes | Input value | |
| Priority1 Priority2 Priority3 Priority4 Priority5 Priority6 Priority7 Priority8 | AlarmPriorityType | No | No | Alarm priority | |
| Delay1 Delay2 Delay3 Delay4 Delay5 Delay6 Delay7 Delay8 | time | No | No | Alarm delay (if zero, no delay is applied) |
Outputs
| Outputs | Name | Data Type | Meaning |
| Alarm1 Alarm2 Alarm3 Alarm4 Alarm5 Alarm6 Alarm7 Alarm8 | AlarmTrigger | Output |
Detailed Function Description
The block generates an alarm if any Input… is active for at least the duration of Delay… with the priority defined by Priority….