Time scheduler, bool

T17_BOOLEAN_SCHEDULER

PROGRAM TEST_T17
   VAR 
        FB : LIB.HVAC.V1_0.T17_BOOLEAN_SCHEDULER := (TPGVALUE := [(STARTTIME := 0, STATE := FALSE),
     (STARTTIME := 210, STATE := TRUE),
      (STARTTIME := 420, STATE := FALSE)],
        EXCEPTIONS := [(STARTTIME := 1000, ENDTIME := 2000, STATE := FALSE)]);
      DT1:DT;
     BOOL1:BOOL;
 END_VAR
 DT1:=getlocaltime();
    FB(CURRENTTIME:=DT1, OUT=>BOOL1);
END_PROGRAM

LIB\HVAC

V1.0

Time scheduler is a source of a binary signal which changes according to a weekly schedule with maximum 42 events (changes of state). Exception events (exceptions) defined by date, time, and state can be inserted.

The output value is recalculated at 30-second intervals.

Input TypeDescription
CURRENTTIME DT Date and time in case that other date and time than system date and time shall be used
DEFAULTVALUEBOOLOutput value if en=false
OUTBOOLCurrent time scheduler state
DescriptionImportance
STATE Current state of the time program
STARTTIME Minutes from the beginning of the day

The time scheduler compares current date and time with the definition table and sends the actual state to the output. The output is either true or false. The time scheduler can be edited from IDE or HMI - LCD display, web interface, touchscreen, SCADA or another client).

Time scheduler is used to enable plant operation according to the operating hours plan, for night depressions, etc. (Use T19_INT_SCHEDULER for multistate output, and T18_REAL_SCHEDULER for direct output of analogue values.)

The image illustrated switching between day and night heating curve. At the daytime the scheduler output is on TRUE, at the nighttime it is on FALSE.

In the editor, the scheduler plan is set up to be TRUE from 6:00 to 22:00, and FALSE otherwise: