Operating hours counter

T32_OPERATING_HOURS

PROGRAM TEST_T32
   VAR 
        BOOL1,BOOL2,BOOL3: BOOL;
        TIME1,TIME2:TIME;
       DT1: DT;
        FB: LIB.HVAC.V1_0.T32_OPERATING_HOURS;
  END_VAR
 FB(BSET:= BOOL1, ENABLED:= BOOL2, IN:= BOOL3,TINIT:= TIME1, OUT=> TIME2, TSET=>DT1);  
END_PROGRAM

LIB\HVAC

V1.0

The block measures total activity time of a binary input, or cumulated operating time of the connected aggregate (pump, fan, boiler).

Input TypeDescription Default value
BSET BOOLRising edge sets the counter to TINIT False
ENABLEBOOLThis input must be TRUE for the block to operateFalse
IN BOOLActivity input False
TINIT TIME“Starting” value after reset, usually 0 0
OutputTyp Description
OUT TIMETotal time the IN input was in TRUE
TSET DT Date and time of last reset (rising edge on BSET) as UTC

The block acts as a stopwatch. Time measuring start is activated by bringing the IN input to True, and stopped by bringing IN to False. The default state is set by a rising edge at bset, while the block writes the TINIT value to the OUT output rather than the cumulated time. This becomes the starting value for further cumulation. TSET records the rising edge time.

The variable PUMP1FB gives the pump operation signal. The cumulated time is recorded in T32 and of the total operation time exceeds PUMP_SERVICE_TIME, an alarm to call for service inspection is generated.