Equipment Failure Evaluation

Lib.Mervis.v1_1.BoilerFailure

Auxiliary block used to evaluate equipment failures.

  • Lib.Mervis

**Obsolete** - replaced by the FailureDetector block.

program test
    var
        boilerfailure: lib.mervis.v1_1.BoilerFailure;
    end_var

    boilerfailure();
end_program
Inputs Name Data typeRetainMust be connectedDescription
Demand bool No Yes Operating demand
Running bool No Yes Running feedback
Failure bool No Yes Failure signal input
Delay time No No Waiting interval for active running feedback
CountLimit uint No No Number of consecutive failures required to trigger a persistent alarm
Timeout time No No Delay before restarting
Outputs Name Data type Description
FailureOutput AlarmTriggerAlarm output

The block evaluates equipment operation and generates a trigger condition for alarm generation. When the Demand command is active, the Running feedback signal is monitored. If it does not become active within the time specified by the Delay input, an alarm is generated.

An alarm is also generated when the Failure input is activated. If the number of consecutive failures (separated by activation and deactivation of the command) is less than CountLimit, an alarm with automatic reset is generated. Otherwise, manual intervention is required to reset the alarm.

The alarm remains active for the period specified by the Timeout parameter. If startup is successful, the failure counter is reset.

The block generates alarms with the following priorities:

  • 32 - alarm requiring external intervention
  • 33 - alarm with automatic reset