Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
en:mervis-analytics:50-data-for-hvac-analytics [2020/04/08 14:27]
j.siroky [Air handling unit]
en:mervis-analytics:50-data-for-hvac-analytics [2020/04/08 16:02] (current)
Line 1: Line 1:
 ====== Data for HVAC analytics ====== ====== Data for HVAC analytics ======
 ==== General information ==== ==== General information ====
-Building operation is (or at least shall be) determined by a schedule. Therefore we need some information about regimes in the building (at least non-stop operation vs. office hours determined operation). This applies to all analytical topics listed below. +Building operation is (or at least shall be) determined by a schedule. Therefore we need some information about regimes in the building (at least non-stop operation vs. office hours determined operation). We do not read this information directly from BMS. It shall be defined by facility management in order to validate BMS setting. This applies to all analytical topics listed below. 
  
-We do not require outdoor temperature, we use independent data source. +We do not require outdoor temperature (humidity, pressure,...), we use independent data source. 
  
 Bellow is a list of recommend variables for each analytical topic. Bellow is a list of recommend variables for each analytical topic.
Line 9: Line 9:
 ^ Signal ^ Type ^ Note ^ ^ Signal ^ Type ^ Note ^
 | Supply water temperature | measurement and setpoint |  | | Supply water temperature | measurement and setpoint |  |
 +| Return water temperature | measurement |  |
 | Pump | measurement or setpoint | | | Pump | measurement or setpoint | |
 | Valve | setpoint | | | Valve | setpoint | |
Line 21: Line 22:
  
 ==== Air handling unit ==== ==== Air handling unit ====
-AHU is more complex appliance and there is no unified data set for analysis. Usually, AHU is described by 15 - 30 relevant variables. +AHU is complex appliance and there is no unified set of variables that are need for AHU analysis. We try to use all data that are provided. Usually, AHU is described by 15 - 30 relevant variables. 
  
 +Information about heat recovery type (plate, wheel or glycol) is also needed as well as operation schedule.
  
 ^ Signal ^ Type ^ Note ^ ^ Signal ^ Type ^ Note ^
  • © Energocentrum Plus, s.r.o. 2017 - 2024