====== Equithermal Curve (v1.0) ====== {{:cs:mervis-ide:35-help:equithermalcurve.png}} ==== Full Name ==== Lib.Mervis.v1_0.EquithermalCurve ==== Required Project References ==== * Lib.Mervis ===== Description ===== Block for calculating the heating medium temperature according to the equithermal curve. ===== Usage in ST ===== program test var eq: lib.mervis.v1_0.EquithermalCurve; end_var eq(); end_program ===== Inputs ===== |Inputs |Name |Data Type|Retain|Mandatory Connection|Meaning | |In |real |No |Yes |Outdoor temperature | | |t_i |real |Yes |No |Calculated indoor temperature| | |t_emin |real |Yes |No |Minimum outdoor temperature | | |t_w1max |real |Yes |No |Maximum heating medium temperature | | |t_w2max |real |Yes |No |Minimum heating medium temperature | | |n |real |Yes |No |Temperature exponent | | ===== Outputs ===== |Outputs |Name |Data Type|Meaning | |t_flow |real |Calculated heating medium temperature | |t_return|real |Calculated return heating medium temperature | ===== Detailed Function Description ===== The block calculates the heating medium temperature based on the outdoor temperature. Recommended values for the parameter //n//: ^ Heating Type ^ Parameter //n// Value ^ | Underfloor heating | 1.10 | | Panel radiators | 1.26 to 1.33 | | Tubular bathroom radiators | 1.20 to 1.30 | | Radiators according to DIN 4703 | 1.30 | | Convectors | 1.30 to 1.50 |