Lib.Mervis.v1_5.ModulatedBoiler
Block used for controlling the performance of a boiler with a modulated burner and a circulation pump.
program test var modulatedBoiler: lib.mervis.v1_5.ModulatedBoiler; end_var modulatedBoiler(); end_program
Inputs | Name | Data Type | Retain | Required Connection | Meaning |
OperatingMode | Lib.Mervis.v1_0.OperatingModeType | Yes | No | Boiler operating mode | |
PumpOperatingMode | Lib.Mervis.v1_0.OperatingModeType | Yes | No | Circulation pump operating mode | |
ManualPower | real | Yes | No | Boiler power in manual mode | |
OutputTemperature | real | No | Yes | Output temperature | |
BoilerDemand | Lib.Mervis.v1_1.StageControlType | No | Yes | Combined boiler demand from the cascade controller | |
Running | bool | No | No | Feedback signal of boiler operation | |
Failure | bool | No | No | Feedback signal of boiler failure | |
PumpRunning | bool | No | No | Feedback signal of circulation pump operation | |
PumpFailure | bool | No | No | Feedback signal of circulation pump failure | |
ResetRuntime | bool | No | No | Reset runtime hours | |
MinimalOutput | real | No | No | External input for defining the minimum output temperature (if zero, it is not used) | |
Xp | real | No | No | PI controller - proportional band | |
Ti | real | No | No | PI controller - integral time | |
MaxOutputTemperature | real | No | No | Maximum output temperature, exceeding it is considered a fault | |
FailureDelay | time | No | No | Interval waiting for active boiler operation feedback | |
FailureCountLimit | uint | No | No | Number of consecutive boiler errors before it is permanently marked as non-functional | |
FailureTimeout | time | No | No | Time after an unsuccessful boiler start before retrying | |
LimitingXp | real | No | No | PI controller for limiting the maximum output temperature - proportional band | |
LimitingTi | real | No | No | PI controller for limiting the maximum output temperature - integral time | |
UseLocalOutputTemperature | bool | No | No | Determines whether the control uses the common output temperature or its own (= true) | |
RunTimeSource | Lib.Mervis.v1_0.RunTimeSourceType | No | No | Determines how the boiler runtime hours are counted | |
PumpRunDownTime | time | No | No | Run-down time of the circulation pump after the boiler is removed from the cascade | |
PumpFailureDelay | time | No | No | Interval waiting for active circulation pump operation feedback |
Outputs | Name | Data Type | Meaning |
State | Lib.Mervis.v1_1.StageInfoType | Combined boiler state to the cascade controller | |
Demand | real | Required boiler power | |
PumpDemand | bool | Command for the circulation pump | |
RunTimeInHours | udint | Boiler runtime in whole hours | |
FailureOutput | bool | Boiler fault | |
PumpFailureOutput | bool | Circulation pump fault | |
AlarmsStatus | Lib.Mervis.v1_0.AlarmsStatus | Combined interface for alarm indication | |
RunTime | time | Boiler runtime |
Blocks | Name | Data Type | Meaning | ||||||||||||||||||||
FailureFb | Lib.Mervis.v1_0.FailureDetector | Block for evaluating boiler failure | |||||||||||||||||||||
Alarms | Lib.Mervis.v1_0.AlarmsExtender4 | Alarm function block | Alarm Input | Priority | Meaning | Alarm1 | 32/33 | Boiler fault | Alarm2 | - | Not used | Alarm3 | 32 | Pump fault | Alarm4 | 33 | Boiler overheat |