Alarm Aggregator (v1.1)

Full Name

Lib.Mervis.v1_1.AlarmsAggregator

Required Project References

Description

[todo]

Usage in ST

program test
    var
        alr: lib.mervis.v1_1.AlarmsAggregator;
    end_var

    alr();
end_program

Usage in FUPLA

Used Alarm Priorities in Lib.Mervis

Assignment

PriorityClassMeaning
0 to 15 0 Total failure, results in blocking the operation enablement.
16 to 311 Total failure, results in blocking the operation enablement.
32 to 472 General failure.
48 to 633 General failure.

Alarm Class is used to group multiple priorities into one category. This category is then used for reporting between different alarm blocks (AlarmsAggregator, AlarmsExtender, and AlarmsCoupler) using the AlarmsStatus structure.

If the priority is odd, it will automatically reset after it ceases.

For even classes, the corresponding alarm output (Alarm*Flag) remains active even in the remembered alarm state (i.e., Memory, AckedMemory). For odd classes, it is active only if the alarm itself is active (i.e., Active, ActiveAcked).

Inputs

Name Data TypeRetainMandatory to Connect Meaning
Alarm1 AlarmTriggerNo No Alarm Input 1
Alarm2 AlarmTriggerNo No Alarm Input 2
Alarm3 AlarmTriggerNo No Alarm Input 3
Alarm4 AlarmTriggerNo No Alarm Input 4
Alarm5 AlarmTriggerNo No Alarm Input 5
Alarm6 AlarmTriggerNo No Alarm Input 6
Alarm7 AlarmTriggerNo No Alarm Input 7
Alarm8 AlarmTriggerNo No Alarm Input 8
Reset bool No No Reset Alarms
Acknowledge bool No No Acknowledge Alarms
Enable bool No No External enable for subsequent technology (enables the output RunEnabled)
Status AlarmsStatusNo No Extended input for additional alarms
StartupDelay time No No Startup delay after all alarms are reset
HornActiveInLowPriobool No No If true, the horn is active even when a low priority alarm occurs. This only works for alarms directly on the aggregator, not for extended blocks connected via Status

Outputs

Name Data Type Meaning
Alarm1Flag bool Indication of non-reset alarm 1 (explanation see alarm priorities)
Alarm2Flag bool Indication of non-reset alarm 2
Alarm3Flag bool Indication of non-reset alarm 3
Alarm4Flag bool Indication of non-reset alarm 4
Alarm5Flag bool Indication of non-reset alarm 5
Alarm6Flag bool Indication of non-reset alarm 6
Alarm7Flag bool Indication of non-reset alarm 7
Alarm8Flag bool Indication of non-reset alarm 8
RunEnabled bool Enable input for subsequent technology
StartupCounter time Countdown of remaining time until enable input activation
SummaryTotalAlarm bool Combined indication of high-priority alarm
SummaryLowPrioAlarmbool Combined indication of low-priority alarm
WarningHorn bool Output for horn control
AlarmLight bool Output for fault light control
StatusOut AlarmsStatusOutput for connection to superior alarm blocks
Local VariablesName Data TypeRetain Meaning
AlarmFlags array[1..8] of AlarmPointYes States of individual alarms

Detailed Function Description

[todo]

Versions