Equipment Failure Detector

Function Block Name

Lib.Mervis.v1_1.FailureDetector

Description

Core block used to evaluate equipment operation and detect failures.

Required Project References

Block Usage Restrictions

None - current standard block.

Usage in ST

program test
    var
        failuredetector: lib.mervis.v1_1.FailureDetector;
    end_var

    failuredetector();
end_program

Input and Output Description

Inputs Name Data typeRetainMust be connectedDescription
Demand bool No Yes Operating demand
Feedback bool No Yes Running feedback
Failure bool No Yes Failure signal input
Delay time No No Waiting interval for active running feedback
CountLimit uint No No Number of consecutive failures required to trigger a persistent alarm
Timeout time No No Delay before restarting
Outputs Name Data type Description
FailureOutput AlarmTriggerAlarm output

Detailed Function Description

The block evaluates equipment operation and generates a trigger condition for alarm generation. When the Demand command is active, the Feedback signal is monitored. If it does not become active within the time specified by the Delay input, an alarm is generated.

An alarm is also generated when the Failure input is activated. If the number of consecutive failures (separated by activation and deactivation of the command) is less than CountLimit, an alarm with automatic reset is generated. Otherwise, manual intervention is required to reset the alarm.

The alarm remains active for the period specified by the Timeout parameter. If startup is successful, the failure counter is reset.

The block generates alarms with the following priorities: