====== Equipment Failure Evaluation ====== {{:cs:mervis-ide:35-help:boilerfailure.png}} ===== Function Block Name ===== Lib.Mervis.v1_0.BoilerFailure ===== Description ===== Auxiliary block used to evaluate equipment failures. ===== Required Project References ===== * Lib.Mervis ===== Block Usage Restrictions ===== **Obsolete** - nahrazen blokem [[en:mervis-ide:35-help:035-software_basic:060-libraries:060-lib-mervis:015-utilities:030-types:boilerfailure_v1.1|BoilerFailure v1.1]] ===== Usage in ST ===== program test var boilerfailure: lib.mervis.v1_1.BoilerFailure; end_var boilerfailure(); end_program ===== Input and Output Description ===== |Inputs |Name |Data type|Retain|Must be connected|Description| |Demand |bool |No |Yes |Operating demand | | |Running |bool |No |Yes |Running feedback | | |Failure |bool |No |Yes |Failure signal input| | |Reset |bool |No |Yes |Failure reset | | |Delay |time |No |No |Waiting interval for active running feedback| | |CountLimit |uint |No |No |Number of consecutive failures required to trigger a persistent alarm| | |Timeout |time |No |No |Delay before restarting| | |Outputs |Name |Data type|Description| |FailureOutput |bool |Alarm output| | ===== Detailed Function Description =====