====== Time scheduler, integer ======
{{:en:mervis-ide:35-help:t19.png}}
===== Block name =====
T19_INT_SCHEDULER
===== ST call =====
PROGRAM TEST_T19
VAR
FB : LIB.HVAC.V1_0.T19_INT_SCHEDULER := (TPGVALUE := [(STARTTIME := 0, STATE := 0),
(STARTTIME := 1630, STATE := 7),
(STARTTIME := 1750, STATE := 0),
(STARTTIME := 3070, STATE := 7),
(STARTTIME := 3190, STATE := 0),
(STARTTIME := 65535, STATE := 0)],
EXCEPTIONS := [(STARTTIME := 1000, ENDTIME := 2000, STATE := 0)]);
DT1:DT;
INT1:UINT;
END_VAR
DT1:=getlocaltime();
FB(CURRENTTIME:=DT1, OUT=> INT1);
END_PROGRAM
===== Library =====
LIB\HVAC
===== Version =====
V1.0
===== Description =====
Time scheduler is a source of an integer variable which value changes according to a weekly schedule with maximum 42 events (changes of state). Exception events (exceptions) defined by date, time, and state can be inserted.
The output value is recalculated at 30-second intervals.
===== Inputs =====
|Input |Type|Description |
|CURRENTTIME |DT |Date and time in case that other date and time than system date and time shall be used|
|DEFAULTVALUE|UINT|Output value if en=false |
===== Outputs =====
|OUT|UINT|Current time schedule state|
===== Description of internal structures =====
|Description|Importance |
|STATE |Current state of the time program |
|STARTTIME |Minutes from the beginning of the day|
===== Function =====
The time scheduler compares current date and time with the definition table and sends the actual state to the output. The output is a integer value. The possible scheduler states are defined The time scheduler can be edited from IDE or HMI - LCD display, web interface, touchscreen, SCADA or another client).
===== Application example =====
Time scheduler is used to specify variable setpoints in time directly. (Use [[en:mervis-ide:35-help:035-software_basic:060-libraries:040-hvac:020-time-programs:005-t17_boolean_scheduler|T17_BOOLEAN_SCHEDULER]] for boolean (on/off) output, and [[en:mervis-ide:35-help:035-software_basic:060-libraries:040-hvac:020-time-programs:025-t18_real_scheduler|T18_REAL_SCHEDULER]] for direct outout of analogue setpoints.) At the image below, T19 is used to switch between Off / Stage 1 / Stage 2 / CO2 control modes. In the CO2 mode, the fan stages are changed according to the CO2 concentration in the room.
{{:en:mervis-ide:35-help:t19_example.png}}
In the editor there is a morning purge at 7:00 with Stage 2, Stage 1 is active in the morning and in the evening, while in the daytime the CO2 control is active.
{{:en:mervis-ide:35-help:t19_example2.png}}