PID controller - heating

Block name

B37_REVERSE_PID_CONTROLLER

ST call

PROGRAM B37_TEST
VAR 
   XIN,WIN,COOLING:REAL;   
    FB: LIB.CORE.V1_0.B37_REVERSE_PID_CONTROLLER;
END_VAR
    FB(X:=XIN, W:=WIN, OUT=>COOLING);
END_PROGRAM

Library

LIB\CORE

Version

V1.0

Description

The block is an implementation of a PID controller (with parameters: P-band, Integration constant, Derivative constant, Offset, Min and Max values, and output value of an inactive controller).

Inputs

Input Type Description Default value
W REAL Setpoint (usually temperature). 0
X REAL Measured value (usually temperature). 0
CONTROLLERTYPECONTROLLERTYPEController type (cooling/heating). cooling
BP BOOL When set to TRUE, the I part is disabled (the controller acts as a P controller)False
ENABLED BOOL Controller enable (FALSE = controller is deactivated). True
XP REAL Proportional band. 30
OFF REAL Offset, added to the setpoint W. 0
TI REAL Integration constant 120
TD REAL Derivative constant 1
MIN REAL Minimum output value OUT (usually 0). 0
MAX REAL Maximum output value OUT (usually 100). 100
DISVAL REAL Value of the OUT output when the controller is deactivated (ENABLED=FALSE). 0

Outputs

Output TypeDescription
OUT REALOutput signal (mostly valve or damper, 0 to 100%).
PFACTORREALP-part of the output signal
IFACTORREALI-part of the output signal
DFACTORREALD-part of the output signal

Function

There is a control deviation at the controller input, E=(W+OFF)-X. The controller output OUT is given by the relation OUT=-100/Xp*(E+1/Ti*∫e+Td*e')+MIN, where the first part is the proportional part (P), the second part is the integration part (I), and the third part is the derivative part (D). The resulting value is finally limited by MIN and MAX, see figure at block B32. The I-part helps to achieve the exact control value.

The D-part is calculated according to the figure below. To simplify the issue, let us assume Ti=0 and the I part = 0. When W+OFF=0 and the X input goes from 0 to -1 in time t=Td, then the D-part has a constant value of 100, and the P-band rises to 100/Xp.

The BP input sets the I-and D-parts to 0, if set to true.

The ENABLED parameter switches the controller off (ENABLED=FALSE, controller disabled, and OUT=DISVAL). Function in case of incorrect setting: Xp⇐ 0, then OUT=MAX for x>=W+OFF, and OUT=MIN for X<W+OFF. Note that the I- and D-parts are 0 in this case. If Ti⇐ 0 then the I constant is considered to be 0. If Td⇐ 0 then the D constant is considered to be 0. If  MAX<MIN then OUT=MAX (minimum of both).

Application example