- | ====== Modbus server setup ====== | ||
- | |||
- | Modbus server provides data to a 3rd party PLC which is not compatible with the Mervis communication protocol. Both Modbus RTU (except for wPLC750-8101, | ||
- | |||
- | In the example, two mark320 controllers will be connected over their COM4 ports where they will communicate over Modbus RTU, using Modbus address of 1, and register 1 to share data. PLC2 represents the 3rd party PLC (client PLC) which reads data over Modbus. PLC2 has a channel created, and a Generic device that reads a Modbus value from Register 1. | ||
- | |||
- | At the server PLC (PLC) add a server channel: right-click PLC and Add server channel. | ||
- | |||
- | {{: | ||
- | |||
- | In Channel Properties, select ModbusServer, | ||
- | |||
- | {{: | ||
- | |||
- | Add a server device into the server channel. For Modbus TCP, only one device is allowed. | ||
- | |||
- | {{: | ||
- | |||
- | In case of Serial channel, enter only the Modbus link address (1...255) as Device address in the device properties. | ||
- | |||
- | {{: | ||
- | |||
- | In case of a TCP server, enter the IP address of the device. Normally, it is localhost (127.0.0.1) \\ | ||
- | " | ||
- | |||
- | In the " | ||
- | |||
- | Right click the workspace to insert a new register or variable. | ||
- | |||
- | {{: | ||
- | |||
- | The "Add Variable" | ||
- | |||
- | {{: | ||
- | |||
- | Analog functions (Holding reg. and Input reg.) and Digital functions (Coils and Inputs) may have the same " | ||
- | Convert to INT - Converting to Integer, use e.g. for Real variables.\\ | ||
- | Identity - Keeping the format unchanged.\\ | ||
- | Multiply by 100 - Value is multiplied by 100, and written to the Modbus table. This allows communicating e.g. temperatures as integers, a temperature of e.g. 23.56 °C is communicated as 2356, and must be divided in the Modbus client after reading. This is called a "HVAC integer format" | ||
- | Multiply by 10 - Same as above, multiplied by 10.\\ | ||
- | Divide by 100 - Value is divided by 100, and written to the Modbus table. May be used to fit long values into the 16-bit Modbus register.\\ | ||
- | Divide by 10 - Same as above, divided by 10. | ||
- | |||
- | {{: | ||
- | |||
- | {{: | ||
- | |||
- | After all required variables have been inserted into the Modbus table, deploy the solution into the PLC. | ||
- | |||
- | ==== Note ==== | ||
- | |||
- | For data types larger than 16 bits (1 register), 2 or more registers must be reserved in the Modbus table. E.g. a REAL value occupies 32 bits = 2 registers. Use the Identity transform then. | ||
- | |||
- | ===== Example ===== | ||
- | |||
- | The example below shows a Modbus server with starting element of 1, where the plc1 variable is mapped, as a Holding register. On the client side, the Modbus parameters must be set as Read / Write holding register No. 1. After deploy, the value can be changed on the client PLC and the changes are written into the server PLC. | ||
- | |||
- | {{: | ||
- | |||
- | Test the communication after deploying both projects. Entering a new value in plc1 results in change in the device_var1 variable. | ||
- | |||
- | {{: | ||
- | |||
- | Similarly, more variables can be enterd in a project. | ||