Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
en:mervis-ide:30-communication-protocols:30-modbus [2018/11/20 10:35]
m.chlupac [Columns]
en:mervis-ide:30-communication-protocols:30-modbus [2021/04/08 13:04] (current)
Line 10: Line 10:
 ^ StationNumber  | Modbus server address                                                                                               | ^ StationNumber  | Modbus server address                                                                                               |
 ^ Name           | Variable name                                                                                                       | ^ Name           | Variable name                                                                                                       |
-^ Element        | Register address                                                                                                    |+^ Element        | Register/Coil address. \\ The concrete bit position (LSB=.1 to MSB=.16) or byte (.Lo or .Hi) can be specified for Registers - see examples below |
 ^ Count          | Number of modbus elements to be read/written                                                                        | ^ Count          | Number of modbus elements to be read/written                                                                        |
 ^ Function       | Coil/DiscreteInput/InputRegister/HoldingRegister                                                                    | ^ Function       | Coil/DiscreteInput/InputRegister/HoldingRegister                                                                    |
-^ Writable       | 0/1                                                                                                                 |+^ Writable       Read only = 0, Read/Write =                                                                                       |
 ^ StType         | Standard Mervis IDE variable type                                                                                   | ^ StType         | Standard Mervis IDE variable type                                                                                   |
-^ ByteOrder      | Leave empty for default byte order                                                                                  |+^ ByteOrder      | Leave empty for default byte order or specify correct byte positions as numbers from 1 to 8 (eg. 1234/3412/4321/2143 for 32 bit number) |
 ^ K              | Transformation parameter for y = Kx + Q                                                                             | ^ K              | Transformation parameter for y = Kx + Q                                                                             |
 ^ Q              | Transformation parameter for y = Kx + Q                                                                             | ^ Q              | Transformation parameter for y = Kx + Q                                                                             |
Line 32: Line 32:
 1,Variable006,505,2,InputRegister,0,Real,3412,,,,,, 1,Variable006,505,2,InputRegister,0,Real,3412,,,,,,
 1,Variable007,507,2,InputRegister,0,Real,,,,,,, 1,Variable007,507,2,InputRegister,0,Real,,,,,,,
-1,Variable008,407,1,HoldingRegister,0,Int,,,,,,,+1,Variable008,407,1,HoldingRegister,0,Int,,0.1,,,,,
 1,Variable009,408,1,HoldingRegister,0,Int,,,,,,, 1,Variable009,408,1,HoldingRegister,0,Int,,,,,,,
 1,Variable010,409,1,HoldingRegister,0,Int,,,,,,, 1,Variable010,409,1,HoldingRegister,0,Int,,,,,,,
Line 44: Line 44:
 1,Variable018,5,2,HoldingRegister,0,Real,,,,,,, 1,Variable018,5,2,HoldingRegister,0,Real,,,,,,,
 1,Variable019,7,2,HoldingRegister,0,Real,,,,,,, 1,Variable019,7,2,HoldingRegister,0,Real,,,,,,,
 +</code>
 +
 +<code csv ModbusDefinition2.csv>StationNumber,Name,Element,Count,Function,Writable,StType,ByteOrder,K,Q,X1,Y1,X2,Y2
 +1,Variable001_bit1,1201.1,1,InputRegister,0,Bool,12,,,,,,
 +1,Variable001_bit10,1201.10,1,InputRegister,0,Bool,12,,,,,,
 +1,Variable001_Hi,1201.Hi,1,InputRegister,0,Usint,12,,,,,,
 </code> </code>
  
  