Modbus

Import Device Definition

You can use simple CSV file to import definition of modbus device into your Mervis IDE project.

Columns

Name Description
StationNumber Modbus server address
Name Variable name
Element Register/Coil address.
The concrete bit position (LSB=.1 to MSB=.16) or byte (.Lo or .Hi) can be specified for Registers - see examples below
Count Number of modbus elements to be read/written
Function Coil/DiscreteInput/InputRegister/HoldingRegister
Writable Read only = 0, Read/Write = 1
StType Standard Mervis IDE variable type
ByteOrder Leave empty for default byte order or specify correct byte positions as numbers from 1 to 8 (eg. 1234/3412/4321/2143 for 32 bit number)
K Transformation parameter for y = Kx + Q
Q Transformation parameter for y = Kx + Q
X1 Alternative definition for y = Kx + Q, where the parameters are computed from [X1,Y1], [X2,Y2] points of the line.
Y1 Alternative definition for y = Kx + Q, where the parameters are computed from [X1,Y1], [X2,Y2] points of the line.
X2 Alternative definition for y = Kx + Q, where the parameters are computed from [X1,Y1], [X2,Y2] points of the line.
Y2 Alternative definition for y = Kx + Q, where the parameters are computed from [X1,Y1], [X2,Y2] points of the line.
ModbusDefinition.csv
StationNumber,Name,Element,Count,Function,Writable,StType,ByteOrder,K,Q,X1,Y1,X2,Y2
1,Variable001,1201,1,InputRegister,0,Int,12,,,,,,
1,Variable002,1202,1,InputRegister,0,Int,12,,,,,,
1,Variable003,1203,1,InputRegister,0,Int,12,,,,,,
1,Variable004,501,2,InputRegister,0,Real,3412,,,,,,
1,Variable005,503,2,InputRegister,0,Real,3412,,,,,,
1,Variable006,505,2,InputRegister,0,Real,3412,,,,,,
1,Variable007,507,2,InputRegister,0,Real,,,,,,,
1,Variable008,407,1,HoldingRegister,0,Int,,0.1,,,,,
1,Variable009,408,1,HoldingRegister,0,Int,,,,,,,
1,Variable010,409,1,HoldingRegister,0,Int,,,,,,,
1,Variable011,425,1,HoldingRegister,0,Int,,,,,,,
1,Variable012,426,1,HoldingRegister,0,Int,,,,,,,
1,Variable013,427,1,HoldingRegister,0,Int,,,,,,,
1,Variable014,428,1,HoldingRegister,0,Int,,,,,,,
1,Variable015,429,1,HoldingRegister,0,Int,,,,,,,
1,Variable016,1,2,HoldingRegister,0,Real,,0.1,0,,,,
1,Variable017,3,2,HoldingRegister,0,Real,,,,0,0,20,10
1,Variable018,5,2,HoldingRegister,0,Real,,,,,,,
1,Variable019,7,2,HoldingRegister,0,Real,,,,,,,
ModbusDefinition2.csv
StationNumber,Name,Element,Count,Function,Writable,StType,ByteOrder,K,Q,X1,Y1,X2,Y2
1,Variable001_bit1,1201.1,1,InputRegister,0,Bool,12,,,,,,
1,Variable001_bit10,1201.10,1,InputRegister,0,Bool,12,,,,,,
1,Variable001_Hi,1201.Hi,1,InputRegister,0,Usint,12,,,,,,